Copyright © 2004, Tjernlund Products, Inc. All rights reserved P/N 8504102OWNER INSTRUCTIONS, DO NOT DESTROYRecognize this symbol as an indication of
NOTCH BRACINGIt is recommended and local codes may dictate that the joist be reinforced as outlined below. Bracing of the rim joist is not necessary.
10INSTALLATION OF VENT PIPE If installing the SideShot Vent System on an oil or gas appliance which is not equipped with a draft hood or draft diverte
114. Using a tube cutter, cut the sensing tube 2" from the elbow directed at the vent pipe inlet collar, (See Diagram L). Discard the cut off se
ELECTRICAL WIRING All wiring from the SS1 to the appliance must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, intermedia
13SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R8184 SERIES OR EQUIVALENT PRIMARY CONTROL50/60 HzRWHITEORANGEBLACKHONEYWELLR8
14SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH AN AQUASTATXNRUNIVERSAL CONTROLLERLINE VOLTAGE OIL BURNERPRIMARY CONTROL, BURNERL1NXLJ1J
15SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A HONEYWELL R8184 SERIES OR EQUIVALENT PRIMARY CONTROL AND A BURNER MOTOR POST-PURGE 1.
16SIDESHOT WITH INTEGRAL UC1 CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITION MODULEXNRUNIVERSAL CONTROLLERD/N 9183046-8115 VAC24 VACLEGEND:HONEYWE
DRAFT ADJUSTMENT PROCEDURE17SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 OR 115 VAC STANDING PILOT115V24VDRYOF FURNACE/BOILERINTER
DRAFT ADJUSTMENT PROCEDURE FOR OIL EQUIPMENTThe SideShot Vent system will properly vent a wide range of BTU/hr. input capacities. To compensate for d
1Tjernlund Products welcomes your comments and questions. Address all correspondence to:Customer Service • Tjernlund Products, Inc. • 1601 Ninth Stre
IMPORTANT:The following paragraph describes the initial draft adjustment. It may be necessary to make a slight readjustment to compensatefor various
TROUBLESHOOTING OIL ODORSMany problems can be eliminated quite easily by having the equipment properly set up by a professional oil-heat service contr
LED FAULT INDICATORSFault conditions are indicated by counting the number of times LED #4 (Red) flashes.LED #4 Flashes 2 Times Fan Prover was in elect
Voltage should be the same in both cases, if not rewire per appropriate diagram or confirm burner control(s) are functioning prop-erly. NOTE: If a d
23WHEEL REPLACEMENT (DIAGRAM N)1. Loosen set screw from wheel hub by using a 5/32” allen wrench.2. Twist wheel to loosen and pull off of motor shaft.
2SPECIFICATIONSMotor: 115/1/60, 3300 RPM, 212 watts, 2.28 FLAFan Proving Switch: Non-adjustable set point of -.05" W.C.High Limit: Manual reset
CAUTIONSThe SS1 must be installed by a qualified installer (an individual properly licensed and/or trained) in accordance with all local codes or, in
SS1 WITH INTEGRAL UC1 UNIVERSAL CONTROL BOARD FEATURES# 1. Power supplied by board. Do not supply power to this area or control damage may result.# 2
LED FAULT INDICATORS Fault conditions are indicated by counting the number of times LED #4 (Red) flashes.LED #4 Flashes 2 Times Fan Prover was in elec
PLENUM AND VENT HOOD CLEARANCE FROM COMBUSTIBLESWith an inlet flue gas temperature of 650oF or below, the SS1 has been Listed for the following cleara
INSTALLATIONTools required:• Reciprocating Saw • 1/2", 7/16",5/8" Wrench• Drill and 1/8", 1/4", 1/2" Bits • 1/4" Ma
9. Connect the Plenum to the Vent Hood of the SideShot following the steps on pages 8, 9 and 10. 10. After the SideShot is completely installed, apply